Rotary Piston Liquid Sealed Water Meter
Class C Cold Water Metersr DN15-25(mm)
Information
Application
--Measuring the volume of cold (hot) water passing through the pipeline.
Also suitable for pure water.
Feature
--Low start-up flow rate.
--Volumetric rotary piston principle of measurement.
--DN15~20 is no location limitation for installation.
--Accuracy is not to be affected wherever installed at a horizontal, vertical or inclined pipeline.
--Register is sealed with a special liquid to keep a clear reading in long term service.
--Mechanism use of high-quality material to ensure a stable characteristic.
--Accurate measurement with conformity to ISO 4064 class C.
--On request, the series can be equipped with a kind of remote transmission device.
Working condition
--Water temperature: 0.1℃~50℃ for cold water meter .
--Water pressure: PN16
--Pressure -loss class:△p63
Maximum permissible error
-- From minimum flow -rate (Qmin) inclusive to transitional flow-rate (Qt) exclusive ±5%
-- From transitional flrow-rate (Qt) to overload flow-rate Qmax):±2%
Optional Features
--Accuracy: Class C or R=160.
--Material: Brass body,Plastic Nylon.
--Size: Plastic body: DN15-20; Brass body: DN15-25
--Color can be change on body and cover.
--Register: Liquid Sealed.Different register can choose
Flow Technique Specification
Size |
DN |
15 |
20 |
25 |
|
Class |
C |
C |
C |
||
Qmax Overload Flow |
M3/h |
3 |
5 |
7 |
|
Qn Permanent Flow |
1.5 |
2.5 |
3.5 |
||
Qt Transitional Flow |
L/h |
22.5 |
37.5 |
52.5 |
|
Qmin Minimum Flow |
15 |
25 |
35 |
||
Minimum Reading |
M3 |
0.05 |
0.05 |
0.05 |
|
Maximum Reading |
9999.9999 |
9999.9999 |
9999.9999 |
||
Max.Pressure (Bar) |
16 |
16 |
16 |
||
Pressure Loss (△P) |
63 |
63 |
63 |
||
Max.Temperature |
T=50 |